SECTION 28 15 00
INTRUSION DETECTION
28 15 00-2 13-HC1-033
B. UPS
1. APC
2. Best
3. Tripp-Lite
C. Existing Security Contractor:
Schmidt Security
241 Mansfield Industrial Parkway
Mansfield, Ohio 44903
(866) 526-4747 Nate Huffman
PART 2 PRODUCTS
2.01 CONTROL UNIT
A. Control unit shall contain all necessary components to provide complete control, testing
and indicating facilities for the entire security alarm and access control system. The unit
shall have battery back-up as required. Provide a DMP XR500N control panel with the
following features:
1. Expansion to a total of at least 10,000 user codes with 99 user profile definitions.
2. 16 independent door/keypad addresses, each with four zones.
3. 20 holiday dates for custom holiday scheduling by area.
4. A total door access granted event buffer of at least 10,000 events.
5. Anti-passback access control selectable by area and user.
6. Four shift schedules per area.
7. A total of at least 100 programmable output relay schedules.
8. 32 individual reporting areas.
9. Built-in bell and telephone line supervision.
B. The system areas and zones shall be programmable, and the system shall store, log, display,
and transmit specific custom designations for system areas, zones, and user names.
C. To ensure continued, one-call support, the system shall be constructed of sensing
components provided directly by the system manufacturer, such as power supplies, motion
detectors, door and window position switches, glass break detectors, or other sensing
devices that the manufacturer offers.
D. The system controller, user interfaces, zone input devices, relay output devices, and the
system signal receiving equipment shall be engineered, manufactured, assembled, and must
be distributed from a location within the United States of America.
E. The system shall support user interaction by way of a keypad, web browser, system
software, key switch, or radio frequency wireless control, using integrated or auxiliary
devices provided by the system manufacturer.
F. The system shall support controller zone input connections, system keypads, system zone
expansion modules, and wireless zone input modules, and must support zone input
connections by way of at least two competitive products. The system shall offer a seamless
integrated compatibility with hard-wire and/ or wireless zone expansion equipment for at
least 200 wireless zones and/ or a maximum of 574 hardwired zones.